[[Image:komfovent_200ve_wiring_diagram.png|300px|right]][[Image:komfovent_c4_plus_logic_board_front.jpg|300px|right]][[Image:komfovent_c4_plus_logic_board_back.jpg|300px|right]][[Image:komfovent_200_dissassembly_diagram.png|300px|right]]Domekt Komfovent C4 is a AHU (Air Handling Unit) for use in a balanced HVAC system. The C4 is an older standard use from approx. 2011 to 2016.
[[Image:komfovent_200ve_wiring_diagram.png|300px|right]][[Image:komfovent_c4_plus_logic_board_front.jpg|300px|right]][[Image:komfovent_c4_plus_logic_board_back.jpg|300px|right]][[Image:komfovent_200_dissassembly_diagram.png|300px|right]]Domekt Komfovent C4 control board is a AHU (Air Handling Unit) for use in a balanced HVAC system. The C4 is an older standard use from approx. 2010 to 2016.


If you have a unit without a control panel or want to interface the unit with an external automation. ex. Home Assistant, the following data will make that possible.
If you have a unit without a control panel or want to interface the unit with an external automation. ex. Home Assistant, the following data will make that possible.
Line 5: Line 5:
To make sure the unit works at all, jump the FC-wires together and the unit should start spinning at max. after three seconds. This confirms that the MCU works as expected.
To make sure the unit works at all, jump the FC-wires together and the unit should start spinning at max. after three seconds. This confirms that the MCU works as expected.


* [[Media:Domekt_Vortvent-Komfovent-Modbus-registerlijst-C4-regeling-EN-2016.pdf|Domekt Komfovent C4 Modbus Register Document]]
* [[Media:Domekt_Vortvent-Komfovent-Modbus-registerlijst-C4-regeling-EN-2016.pdf|Domekt Komfovent C4 Modbus Register Document]] (PDF)
* [[Media:Komfovent C4 Plus modbus description_senas.pdf|Domekt Komfovent C4 Plus Modbus Register Document]]
* [[Media:Komfovent C4 Plus modbus description_senas.pdf|Domekt Komfovent C4 Plus Modbus Register Document]] (PDF)
* [[Media:Domekt_air_handling_c4_plus_install.pdf|Domekt Komfovent C4 (buttons) Installation and Operation Manual]]
* [[Media:Domekt_air_handling_c4_plus_install.pdf|Domekt Komfovent C4 (buttons) Installation and Operation Manual]] (PDF)
* [[Media:DOMEKT_automatika_c4_c4_plus_EN.pdf|Domekt Komfovent C4 (buttons) and C4 Plus (LCD) Installation and Operation Manual]]
* [[Media:DOMEKT_automatika_c4_c4_plus_EN.pdf|Domekt Komfovent C4 (buttons) and C4 Plus (LCD) Installation and Operation Manual]] (PDF)


== Tools ==
== Tools ==
Line 131: Line 131:


=== General ===
=== General ===
13 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 140: Line 142:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 99999
| 9999
| Read/write
| Read/write
| Integer
| Integer
Line 147: Line 150:
| AHU start/stop control
| AHU start/stop control
| 1-Start, 0-Stop
| 1-Start, 0-Stop
| -
|-
|-
| 10000
| 10000
Line 154: Line 158:
| Season (heating permitted or prohibited)
| Season (heating permitted or prohibited)
| 1-Winter, 0-Summer (heater off)
| 1-Winter, 0-Summer (heater off)
| 1
|-
|-
| 10001
| 10001
Line 161: Line 166:
| Alarm status (warnings)
| Alarm status (warnings)
| 14-Service, 13-Heater off, 11-Rotor stop
| 14-Service, 13-Heater off, 11-Rotor stop
| -
|-
|-
| 10002
| 10002
Line 166: Line 172:
| Binary
| Binary
| 0x0..0xF [b3-b0, 0..1]<br>Ex. 0x01=>64=>00000001<br>b0=1, rotating heat exchanger
| 0x0..0xF [b3-b0, 0..1]<br>Ex. 0x01=>64=>00000001<br>b0=1, rotating heat exchanger
| DIP switch status
| System configuration/DIP switch status
| b0-Heat exchange type (0-RECU/1-REGO), <br>b1-Heater type (0-Electric/1-Water), <br>b2-Fan type (0-AC/1-EC), <br>b3-OVR-mode (0-All fans/1-Exhaust fan stop)<br>(1-On, 0-Off)
| b0-Heat exchange type (0-RECU/1-REGO), <br>b1-Heater type (0-Electric/1-Water), <br>b2-Fan type (0-AC/1-EC), <br>b3-OVR-mode (0-All fans/1-Exhaust fan stop)<br>(1-On, 0-Off)
| -
|-
|-
| 10003
| 10003
Line 175: Line 182:
| Time, hhmm
| Time, hhmm
| Ex. 8:05 => 0x0805, 18:30 => 0x121E (18=0x12, 30=0x1E)
| Ex. 8:05 => 0x0805, 18:30 => 0x121E (18=0x12, 30=0x1E)
| -
|-
|-
| 10004
| 10004
Line 182: Line 190:
| Day of the week
| Day of the week
| 1-Mon, 2-Tue, 3-Wed, 4-Thu, 5-Fri, 6-Sat, 7-Sun
| 1-Mon, 2-Tue, 3-Wed, 4-Thu, 5-Fri, 6-Sat, 7-Sun
| -
|-
|-
| 10005
| 10005
Line 189: Line 198:
| Month-day date, mmdd
| Month-day date, mmdd
| Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F)
| Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F)
| -
|-
|-
| 10006
| 10006
Line 196: Line 206:
| Year date, yyyy
| Year date, yyyy
| Ex. 2023
| Ex. 2023
| -
|-
|-
| 10007
| 10007
Line 203: Line 214:
| Alarm status (stop flags)
| Alarm status (stop flags)
| b1-Supply sensor B1, <br>b2-Heater overheating, <br>b3-Water temp. low, <br>b4-Rotor stop, <br>b5-Frost possibility, <br>b6-Air temp. high, <br>b7-Air temp. low <br>(1-Fault, 0-None)
| b1-Supply sensor B1, <br>b2-Heater overheating, <br>b3-Water temp. low, <br>b4-Rotor stop, <br>b5-Frost possibility, <br>b6-Air temp. high, <br>b7-Air temp. low <br>(1-Fault, 0-None)
| -
|-
|-
| 10008
| 10008
Line 210: Line 222:
| Alarm status (stop code)
| Alarm status (stop code)
| 3-Rotor stop, <br>4-Heater overheating, <br>9-Supply sensor B1, <br>19-Air temp. low, <br>20-Air temp. high, <br>27-Water temp. low, <br>28-Frost possibility
| 3-Rotor stop, <br>4-Heater overheating, <br>9-Supply sensor B1, <br>19-Air temp. low, <br>20-Air temp. high, <br>27-Water temp. low, <br>28-Frost possibility
| -
|-
|-
| 10009
| 10009
Line 217: Line 230:
| Modbus ID, default 20
| Modbus ID, default 20
| Ex. 20
| Ex. 20
| 20
|-
|-
| 10010
| 10010
Line 224: Line 238:
| External heater control signal type
| External heater control signal type
| 0-0..12V analog voltage-type, <br>1-12V digital PWM-type <br>(always 0 if heater configured as water type)
| 0-0..12V analog voltage-type, <br>1-12V digital PWM-type <br>(always 0 if heater configured as water type)
| -
|-
|-
| 10011
| 10011
Line 231: Line 246:
| Unknown
| Unknown
|  
|  
| -
|-
|-
|}
|}


=== Ventilation ===
=== Ventilation ===
14 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 244: Line 262:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10099
| 10099
Line 251: Line 270:
| Ventilation intensity level (manual mode)
| Ventilation intensity level (manual mode)
| 1-Low fan speed (60VAC), <br>2-Normal fan speed (recommended) (150VAC), <br>3-High fan speed (230VAC)
| 1-Low fan speed (60VAC), <br>2-Normal fan speed (recommended) (150VAC), <br>3-High fan speed (230VAC)
| 2
|-
|-
| 10100
| 10100
Line 258: Line 278:
| Ventilation intensity level current
| Ventilation intensity level current
| 0-Standby, <br>1-Low fan speed, <br>2-Normal fan speed, <br>3-High fan speed, <br>4-Override mode (OVR-register enabled or FC-wiring closed)  
| 0-Standby, <br>1-Low fan speed, <br>2-Normal fan speed, <br>3-High fan speed, <br>4-Override mode (OVR-register enabled or FC-wiring closed)  
| -
|-
|-
| 10101
| 10101
Line 265: Line 286:
| Control mode (Auto/Manual) (no Comfort or Economy mode available)
| Control mode (Auto/Manual) (no Comfort or Economy mode available)
| 0-Manual (preset fan speed), 1-Auto (schedule)
| 0-Manual (preset fan speed), 1-Auto (schedule)
| 0
|-
|-
| 10102
| 10102
Line 272: Line 294:
| Supply ventilation intensity level 1 (EC-type fan)
| Supply ventilation intensity level 1 (EC-type fan)
| 20 to 100% (EC-fan only)
| 20 to 100% (EC-fan only)
| -
|-
|-
| 10103
| 10103
Line 279: Line 302:
| Supply ventilation intensity level 2 (EC-type fan / AC-type fan)
| Supply ventilation intensity level 2 (EC-type fan / AC-type fan)
| 20 to 100% (EC-fan), 0 to 2 (AC-fan)
| 20 to 100% (EC-fan), 0 to 2 (AC-fan)
| 2
|-
|-
| 10104
| 10104
Line 286: Line 310:
| Supply ventilation intensity level 3 (EC-type fan)
| Supply ventilation intensity level 3 (EC-type fan)
| 20 to 100% (EC-fan only)
| 20 to 100% (EC-fan only)
| -
|-
|-
| 10105
| 10105
Line 293: Line 318:
| Supply ventilation intensity level 4 (EC-type fan)
| Supply ventilation intensity level 4 (EC-type fan)
| 20 to 100% (EC-fan only)
| 20 to 100% (EC-fan only)
| -
|-
|-
| 10106
| 10106
Line 300: Line 326:
| Exhaust ventilation intensity level 1 (EC-type fan)
| Exhaust ventilation intensity level 1 (EC-type fan)
| 20 to 100% (EC-fan only)
| 20 to 100% (EC-fan only)
| -
|-
|-
| 10107
| 10107
Line 307: Line 334:
| Exhaust ventilation intensity level 2 (EC-type fan / AC-type fan)
| Exhaust ventilation intensity level 2 (EC-type fan / AC-type fan)
| 20 to 100% (EC-fan), 0 to 2 (AC-fan)
| 20 to 100% (EC-fan), 0 to 2 (AC-fan)
| 2
|-
|-
| 10108
| 10108
Line 314: Line 342:
| Exhaust ventilation intensity level 3 (EC-type fan)
| Exhaust ventilation intensity level 3 (EC-type fan)
| 20 to 100% (EC-fan only)
| 20 to 100% (EC-fan only)
| -
|-
|-
| 10109
| 10109
Line 321: Line 350:
| Exhaust ventilation intensity level 4 (EC-type fan)
| Exhaust ventilation intensity level 4 (EC-type fan)
| 20 to 100% (EC-fan only)
| 20 to 100% (EC-fan only)
| -
|-
|-
| 10110
| 10110
Line 326: Line 356:
| Integer
| Integer
| 0..1
| 0..1
| Override/OVR-mode, enables fan intensity level 4 (maximum) for a set time period
| Override/OVR-mode, enables fan override intensity level for a set time period
| 0-Disable, 1-Enable - DIP switch 4 set to ON will disable the exhaust fan, or OFF to leave both fans running  
| 0-Disable, 1-Enable - DIP switch 4 set to ON will disable the exhaust fan, or OFF to leave both fans running  
| 0
|-
|-
| 10111
| 10111
Line 335: Line 366:
| Override mode timer duration
| Override mode timer duration
| 1 to 90 minutes
| 1 to 90 minutes
| 30
|-
|-
| 10112
| 10112
Line 342: Line 374:
| Override timer count down
| Override timer count down
| 0 to 90 minutes
| 0 to 90 minutes
| -
|-
|-
|}
|}


=== Scheduler ===
=== Scheduler ===
63 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 355: Line 390:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10199
| 10199
Line 362: Line 398:
| Mon1 start time
| Mon1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10200
| 10200
Line 369: Line 406:
| Mon1 stop time
| Mon1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10201
| 10201
Line 376: Line 414:
| Mon2 start time
| Mon2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10202
| 10202
Line 383: Line 422:
| Mon2 stop time
| Mon2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10203
| 10203
Line 390: Line 430:
| Mon3 start time
| Mon3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10204
| 10204
Line 397: Line 438:
| Mon3 stop time
| Mon3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10205
| 10205
Line 404: Line 446:
| Tue1 start time
| Tue1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10206
| 10206
Line 411: Line 454:
| Tue1 stop time
| Tue1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10207
| 10207
Line 418: Line 462:
| Tue2 start time
| Tue2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10208
| 10208
Line 425: Line 470:
| Tue2 stop time
| Tue2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10209
| 10209
Line 432: Line 478:
| Tue3 start time
| Tue3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10210
| 10210
Line 439: Line 486:
| Tue3 stop time
| Tue3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10211
| 10211
Line 446: Line 494:
| Wed1 start time
| Wed1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10212
| 10212
Line 453: Line 502:
| Wed1 stop time
| Wed1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10213
| 10213
Line 460: Line 510:
| Wed2 start time
| Wed2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10214
| 10214
Line 467: Line 518:
| Wed2 stop time
| Wed2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10215
| 10215
Line 474: Line 526:
| Wed3 start time
| Wed3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10216
| 10216
Line 481: Line 534:
| Wed3 stop time
| Wed3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10217
| 10217
Line 488: Line 542:
| Thu1 start time
| Thu1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10218
| 10218
Line 495: Line 550:
| Thu1 stop time
| Thu1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10219
| 10219
Line 502: Line 558:
| Thu2 start time
| Thu2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10220
| 10220
Line 509: Line 566:
| Thu2 stop time
| Thu2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10221
| 10221
Line 516: Line 574:
| Thu3 start time
| Thu3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10222
| 10222
Line 523: Line 582:
| Thu3 stop time
| Thu3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10223
| 10223
Line 530: Line 590:
| Fri1 start time
| Fri1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10224
| 10224
Line 537: Line 598:
| Fri1 stop time
| Fri1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10225
| 10225
Line 544: Line 606:
| Fri2 start time
| Fri2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10226
| 10226
Line 551: Line 614:
| Fri2 stop time
| Fri2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10227
| 10227
Line 558: Line 622:
| Fri3 start time
| Fri3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10228
| 10228
Line 565: Line 630:
| Fri3 stop time
| Fri3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10229
| 10229
Line 572: Line 638:
| Sat1 start time
| Sat1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10230
| 10230
Line 579: Line 646:
| Sat1 stop time
| Sat1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10231
| 10231
Line 586: Line 654:
| Sat2 start time
| Sat2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10232
| 10232
Line 593: Line 662:
| Sat2 stop time
| Sat2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10233
| 10233
Line 600: Line 670:
| Sat3 start time
| Sat3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10234
| 10234
Line 607: Line 678:
| Sat3 stop time
| Sat3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10235
| 10235
Line 614: Line 686:
| Sun1 start time
| Sun1 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10236
| 10236
Line 621: Line 694:
| Sun1 stop time
| Sun1 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10237
| 10237
Line 628: Line 702:
| Sun2 start time
| Sun2 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10238
| 10238
Line 635: Line 710:
| Sun2 stop time
| Sun2 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10239
| 10239
Line 642: Line 718:
| Sun3 start time
| Sun3 start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10240
| 10240
Line 649: Line 726:
| Sun3 stop time
| Sun3 stop time
| Ex. 15:05 => 0x0F05
| Ex. 15:05 => 0x0F05
| -
|-
|-
| 10241
| 10241
Line 656: Line 734:
| Mon1 ventilation level (fan speed)
| Mon1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10242
| 10242
Line 663: Line 742:
| Mon2 ventilation level (fan speed)
| Mon2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10243
| 10243
Line 670: Line 750:
| Mon3 ventilation level (fan speed)
| Mon3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10244
| 10244
Line 677: Line 758:
| Tue1 ventilation level (fan speed)
| Tue1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10245
| 10245
Line 684: Line 766:
| Tue2 ventilation level (fan speed)
| Tue2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10246
| 10246
Line 691: Line 774:
| Tue3 ventilation level (fan speed)
| Tue3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10247
| 10247
Line 698: Line 782:
| Wed1 ventilation level (fan speed)
| Wed1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10248
| 10248
Line 705: Line 790:
| Wed2 ventilation level (fan speed)
| Wed2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10249
| 10249
Line 712: Line 798:
| Wed3 ventilation level (fan speed)
| Wed3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10250
| 10250
Line 719: Line 806:
| Thu1 ventilation level (fan speed)
| Thu1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10251
| 10251
Line 726: Line 814:
| Thu2 ventilation level (fan speed)
| Thu2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10252
| 10252
Line 733: Line 822:
| Thu3 ventilation level (fan speed)
| Thu3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10253
| 10253
Line 740: Line 830:
| Fri1 ventilation level (fan speed)
| Fri1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10254
| 10254
Line 747: Line 838:
| Fri2 ventilation level (fan speed)
| Fri2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10255
| 10255
Line 754: Line 846:
| Fri3 ventilation level (fan speed)
| Fri3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10256
| 10256
Line 761: Line 854:
| Sat1 ventilation level (fan speed)
| Sat1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10257
| 10257
Line 768: Line 862:
| Sat2 ventilation level (fan speed)
| Sat2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10258
| 10258
Line 775: Line 870:
| Sat3 ventilation level (fan speed)
| Sat3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10259
| 10259
Line 782: Line 878:
| Sun1 ventilation level (fan speed)
| Sun1 ventilation level (fan speed)
| 0-Standby, 1-Low, 2-Normal, 3-High
| 0-Standby, 1-Low, 2-Normal, 3-High
| -
|-
|-
| 10260
| 10260
Line 789: Line 886:
| Sun2 ventilation level (fan speed)
| Sun2 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
| 10261
| 10261
Line 796: Line 894:
| Sun3 ventilation level (fan speed)
| Sun3 ventilation level (fan speed)
| 0 to 3
| 0 to 3
| -
|-
|-
|}
|}
Line 801: Line 900:


=== Temperature ===
=== Temperature ===
6 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 810: Line 911:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10299
| 10299
Line 815: Line 917:
| Integer
| Integer
| -300..750
| -300..750
| Supply air temperature, C (after heat exchanger and heater element, to rooms)
| Supply air temperature, C (sensor B1, after heat exchanger and heater element, to rooms)
| -30 to 75C, 10x C, ex. 250 => 25.0C
| -30 to 75C, 10x C, ex. 250 => 25.0C
| -
|-
|-
| 10300
| 10300
Line 824: Line 927:
| Supply set point temperature, C (for calculation of recuperation, heating levels)
| Supply set point temperature, C (for calculation of recuperation, heating levels)
| 10 to 40C, 10x C, ex. 25.0C => 250
| 10 to 40C, 10x C, ex. 25.0C => 250
| 23
|-
|-
| 10301
| 10301
Line 831: Line 935:
| Temperature correction, C (time based, lower or raise temperature in a set period)
| Temperature correction, C (time based, lower or raise temperature in a set period)
| -9 to +9C, 10x C, ex. +4.5C => 45
| -9 to +9C, 10x C, ex. +4.5C => 45
| 0
|-
|-
| 10302
| 10302
Line 838: Line 943:
| Temperature correction start time
| Temperature correction start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10303
| 10303
Line 845: Line 951:
| Temperature correction stop time
| Temperature correction stop time
| Ex. 15:05 => 0x0F05 (15=0x0F, 05=0x05)
| Ex. 15:05 => 0x0F05 (15=0x0F, 05=0x05)
| -
|-
|-
| 10304
| 10304
Line 850: Line 957:
| Integer
| Integer
| -100..1100
| -100..1100
| Water temperature, C (external, if installed, DIP switch 2 set to ON)
| Water temperature, C (external, sensor B5, if installed, DIP switch 2 set to ON)
| -10 to 110C, 10x C, ex. 320 => 32.0C
| -10 to 110C, 10x C, ex. 320 => 32.0C
| -
|-
|-
|}
|}


=== Operation (not in tech doc) ===
=== Operation control panel (not in tech doc) ===
 
29 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 865: Line 975:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10399
| 10399
Line 870: Line 981:
| Binary
| Binary
| 0x0..0xF [b3-b0, 0..1]<br>Ex. 0x01=>64=>00000001<br>b0=1, rotating heat exchanger
| 0x0..0xF [b3-b0, 0..1]<br>Ex. 0x01=>64=>00000001<br>b0=1, rotating heat exchanger
| DIP switch status
| System configuration/DIP switch status
| b0-Heat exchange type (0-RECU/1-REGO), <br>b1-Heater type (0-Electric/1-Water), <br>b2-Fan type (0-AC/1-EC), <br>b3-OVR-mode (0-All fans/1-Exhaust fan stop)<br>(1-On, 0-Off)
| b0-Heat exchange type (0-RECU/1-REGO), <br>b1-Heater type (0-Electric/1-Water), <br>b2-Fan type (0-AC/1-EC), <br>b3-OVR-mode (0-All fans/1-Exhaust fan stop)<br>(1-On, 0-Off)
| -
|-
|-
| 10400
| 10400
Line 879: Line 991:
| AHU start/stop control
| AHU start/stop control
| 1-Start, 0-Stop
| 1-Start, 0-Stop
| -
|-
|-
| 10401
| 10401
Line 886: Line 999:
| Control mode (Auto/Manual) (no Comfort or Economy mode available)
| Control mode (Auto/Manual) (no Comfort or Economy mode available)
| 0-Manual (preset fan speed), 1-Auto (schedule)
| 0-Manual (preset fan speed), 1-Auto (schedule)
| 0
|-
|-
| 10402
| 10402
Line 891: Line 1,005:
| Integer
| Integer
| 1..3
| 1..3
| Ventilation intensity level (manual mode)
| Ventilation intensity level (in manual mode)
| 1-Low fan speed (60VAC), <br>2-Normal fan speed (recommended) (150VAC), <br>3-High fan speed (230VAC)
| 1-Low fan speed (60VAC), <br>2-Normal fan speed (recommended) (150VAC), <br>3-High fan speed (230VAC)
| 2
|-
|-
| 10403
| 10403
Line 900: Line 1,015:
| Ventilation intensity level current
| Ventilation intensity level current
| 0-Standby, <br>1-Low fan speed, <br>2-Normal fan speed, <br>3-High fan speed, <br>4-Override mode (OVR-register enabled or FC-wiring closed)
| 0-Standby, <br>1-Low fan speed, <br>2-Normal fan speed, <br>3-High fan speed, <br>4-Override mode (OVR-register enabled or FC-wiring closed)
| -
|-
|-
| 10404
| 10404
Line 907: Line 1,023:
| Supply fan level 0 set point
| Supply fan level 0 set point
| 0 to 100%
| 0 to 100%
| 0
|-
|-
| 10405
| 10405
Line 914: Line 1,031:
| Supply fan level 1 set point
| Supply fan level 1 set point
| 0 to 100%
| 0 to 100%
| 20
|-
|-
| 10406
| 10406
Line 921: Line 1,039:
| Supply fan level 2 set point
| Supply fan level 2 set point
| 0 to 100%
| 0 to 100%
| 60
|-
|-
| 10407
| 10407
Line 928: Line 1,047:
| Exhaust fan level 0 set point
| Exhaust fan level 0 set point
| 0 to 100%
| 0 to 100%
| 0
|-
|-
| 10408
| 10408
Line 935: Line 1,055:
| Exhaust fan level 1 set point
| Exhaust fan level 1 set point
| 0 to 100%
| 0 to 100%
| 20
|-
|-
| 10409
| 10409
Line 942: Line 1,063:
| Exhaust fan level 2 set point
| Exhaust fan level 2 set point
| 0 to 100%
| 0 to 100%
| 60
|-
|-
| 10410
| 10410
Line 949: Line 1,071:
| Override supply fan level set point
| Override supply fan level set point
| 0 to 100%
| 0 to 100%
| 100
|-
|-
| 10411
| 10411
Line 956: Line 1,079:
| Override exhaust fan level set point (for standby/0%, set DIP switch 4 to ON)
| Override exhaust fan level set point (for standby/0%, set DIP switch 4 to ON)
| 0 to 100%
| 0 to 100%
| 100
|-
|-
| 10412
| 10412
Line 963: Line 1,087:
| Supply set point temperature, C (for calculation of recuperation, heating levels)
| Supply set point temperature, C (for calculation of recuperation, heating levels)
| 0 to 30C, 10x C, ex. 25.0C => 250
| 0 to 30C, 10x C, ex. 25.0C => 250
| 23
|-
|-
| 10413
| 10413
Line 970: Line 1,095:
| Season (heating permitted or prohibited)
| Season (heating permitted or prohibited)
| 1-Winter, 0-Summer (air heating off)
| 1-Winter, 0-Summer (air heating off)
| 1
|-
|-
| 10414
| 10414
Line 977: Line 1,103:
| Temperature correction, C (time based, lower or raise temperature in a set period)
| Temperature correction, C (time based, lower or raise temperature in a set period)
| -9 to +9C, 10x C, ex. +4.5C => 45
| -9 to +9C, 10x C, ex. +4.5C => 45
| 0
|-
|-
| 10415
| 10415
Line 984: Line 1,111:
| Temperature correction start time
| Temperature correction start time
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10416
| 10416
Line 990: Line 1,118:
| 0x0000..0x183B
| 0x0000..0x183B
| Temperature correction stop time
| Temperature correction stop time
| Ex. 15:05 => 0x0F05 (15=0x0F, 05=0x05)
| Ex. 15:05 => 0x0F05 ([https://www.google.com/search?client=firefox-b-d&q=15+in+hex 15=0x0F], [https://www.google.com/search?client=firefox-b-d&q=05+in+hex 05=0x05])
| -
|-
|-
| 10417
| 10417
Line 998: Line 1,127:
| Supply air temperature, C (after heat exchanger and heater element, to rooms)
| Supply air temperature, C (after heat exchanger and heater element, to rooms)
| -30 to 75C, 10x C, ex. 250 => 25.0C
| -30 to 75C, 10x C, ex. 250 => 25.0C
| -
|-
|-
| 10418
| 10418
Line 1,005: Line 1,135:
| Water temperature, C (external, if installed, DIP switch 2 set to ON)
| Water temperature, C (external, if installed, DIP switch 2 set to ON)
| -10 to 110C, 10x C, ex. 320 => 32.0C
| -10 to 110C, 10x C, ex. 320 => 32.0C
| -
|-
|-
| 10419
| 10419
Line 1,012: Line 1,143:
| Recuperation level (rotating heat exchanger, DIP switch 1 set to ON - not adjustable directly only through supply set point temperature)
| Recuperation level (rotating heat exchanger, DIP switch 1 set to ON - not adjustable directly only through supply set point temperature)
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10420
| 10420
Line 1,019: Line 1,151:
| Supply fan level current
| Supply fan level current
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10421
| 10421
Line 1,026: Line 1,159:
| Exhaust fan level current
| Exhaust fan level current
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10422
| 10422
Line 1,033: Line 1,167:
| Electric heater level current (heating element, DIP switch 2 set to OFF)
| Electric heater level current (heating element, DIP switch 2 set to OFF)
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10423
| 10423
Line 1,040: Line 1,175:
| Water heating level current (external, if installed, DIP switch 2 set to ON)
| Water heating level current (external, if installed, DIP switch 2 set to ON)
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10424
| 10424
Line 1,047: Line 1,183:
| Water cooling level current (external, if installed, DIP switch 2 set to ON)
| Water cooling level current (external, if installed, DIP switch 2 set to ON)
| 0 to 100%
| 0 to 100%
| -
|-
|-
|-
|-
Line 1,054: Line 1,191:
| -
| -
| Unknown
| Unknown
| -
|-
|-
| 10426
| 10426
Line 1,061: Line 1,199:
| Alarm status (warnings)
| Alarm status (warnings)
| 14-Service, 13-Heater off, 11-Rotor stop
| 14-Service, 13-Heater off, 11-Rotor stop
| -
|-
|-
| 10427
| 10427
Line 1,068: Line 1,207:
| Alarm status (stop code)
| Alarm status (stop code)
| 3-Rotor stop, <br>4-Heater overheating, <br>9-Supply sensor B1, <br>19-Air temp. low, <br>20-Air temp. high, <br>27-Water temp. low, <br>28-Frost possibility
| 3-Rotor stop, <br>4-Heater overheating, <br>9-Supply sensor B1, <br>19-Air temp. low, <br>20-Air temp. high, <br>27-Water temp. low, <br>28-Frost possibility
| -
|-
|-
|}
|}


=== Alarm history ===
=== Alarm history ===
701 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 1,081: Line 1,223:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10499
| 10499
Line 1,088: Line 1,231:
| Alarm history count
| Alarm history count
| Length of log to keep
| Length of log to keep
| -
|-
|-
| 10500
| 10500
Line 1,095: Line 1,239:
| Alarm1 (newest) year
| Alarm1 (newest) year
| Ex. 2023
| Ex. 2023
| -
|-
|-
| 10501
| 10501
Line 1,102: Line 1,247:
| Alarm1 (newest) month-day
| Alarm1 (newest) month-day
| Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F)
| Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F)
| -
|-
|-
| 10502
| 10502
Line 1,109: Line 1,255:
| Alarm1 (newest) hour-minute
| Alarm1 (newest) hour-minute
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10503
| 10503
Line 1,116: Line 1,263:
| Alarm1 (newest) alarm stop and warning code
| Alarm1 (newest) alarm stop and warning code
| Ex. 14-Service
| Ex. 14-Service
| -
|-
|-
|..
|..
Line 1,130: Line 1,278:
| Alarm50 (oldest) year
| Alarm50 (oldest) year
| Ex. 2023
| Ex. 2023
| -
|-
|-
| 10697
| 10697
Line 1,137: Line 1,286:
| Alarm50 (oldest) month-day
| Alarm50 (oldest) month-day
| Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F)
| Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F)
| -
|-
|-
| 10698
| 10698
Line 1,144: Line 1,294:
| Alarm50 (oldest) hour-minute
| Alarm50 (oldest) hour-minute
| Ex. 08:05 => 0x0805
| Ex. 08:05 => 0x0805
| -
|-
|-
| 10699
| 10699
Line 1,151: Line 1,302:
| Alarm50 (oldest) alarm stop and warning code
| Alarm50 (oldest) alarm stop and warning code
| Ex. 14-Service
| Ex. 14-Service
| -
|-
|-
|}
|}


=== Misc ===
=== Misc ===
4 registers, 4 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 1,164: Line 1,318:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10799
| 10799
Line 1,171: Line 1,326:
| Internal heater level current (heating element, DIP switch 2 set to OFF)
| Internal heater level current (heating element, DIP switch 2 set to OFF)
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10800
| 10800
Line 1,178: Line 1,334:
| External/water heating level current (external, if installed, DIP switch 2 set to ON)
| External/water heating level current (external, if installed, DIP switch 2 set to ON)
| 0 to 100%
| 0 to 100%
| -
|-
|-
| 10801
| 10801
Line 1,185: Line 1,342:
| Service time counter
| Service time counter
| 0 to 100, when reached 100, it is service time (alarm warning 14)
| 0 to 100, when reached 100, it is service time (alarm warning 14)
| -
|-
|-
| 10802
| 10802
Line 1,191: Line 1,349:
| 0..200
| 0..200
| AHU software program version
| AHU software program version
| 100-V1.00
| 100-V1.00, 103-V1.03
| -
|-
|-
| 10889
| 10889
Line 1,199: Line 1,358:
| V1 0.10V calibration value
| V1 0.10V calibration value
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| 0
|-
|-
| 10890
| 10890
Line 1,206: Line 1,366:
| V2 0.10V calibration value
| V2 0.10V calibration value
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| 0
|-
|-
| 10891
| 10891
Line 1,213: Line 1,374:
| External heater level calibration value
| External heater level calibration value
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| 0
|-
|-
| 10892
| 10892
Line 1,220: Line 1,382:
| Return water temperature calibration value
| Return water temperature calibration value
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory)
| 0
|-
|-
|}
|}


=== Control panel (read-only) ===
=== Control panel (read-only) ===
10 registers


{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
{| border="0" cellspacing="0" cellpadding="1" class="wikitable"
Line 1,233: Line 1,398:
| '''Description'''
| '''Description'''
| '''Data values'''
| '''Data values'''
| '''Default value'''
|-
|-
| 10899
| 10899
Line 1,240: Line 1,406:
| AHU start/stop control
| AHU start/stop control
| 1-Start, 0-Stop
| 1-Start, 0-Stop
| -
|-
|-
| 10900
| 10900
Line 1,247: Line 1,414:
| Season (heating permitted or prohibited)
| Season (heating permitted or prohibited)
| 1-Winter, 0-Summer (heater off)
| 1-Winter, 0-Summer (heater off)
| -
|-
|-
| 10901
| 10901
Line 1,254: Line 1,422:
| Control mode (Auto/Manual)
| Control mode (Auto/Manual)
| 0-Manual (preset fan speed), 1-Auto (schedule)
| 0-Manual (preset fan speed), 1-Auto (schedule)
| -
|-
|-
| 10902
| 10902
Line 1,261: Line 1,430:
| Ventilation intensity level current
| Ventilation intensity level current
| 0-Standby, <br>1-Low fan speed, <br>2-Normal fan speed, <br>3-High fan speed, <br>4-Override mode (OVR-register enabled or FC-wiring closed)  
| 0-Standby, <br>1-Low fan speed, <br>2-Normal fan speed, <br>3-High fan speed, <br>4-Override mode (OVR-register enabled or FC-wiring closed)  
| -
|-
|-
| 10903
| 10903
Line 1,268: Line 1,438:
| Supply set point temperature, C
| Supply set point temperature, C
| 10 to 40C, 10x C, ex. 25.0C => 250
| 10 to 40C, 10x C, ex. 25.0C => 250
| -
|-
|-
| 10904
| 10904
Line 1,275: Line 1,446:
| Supply air temperature, C
| Supply air temperature, C
| -30 to 75C, 10x C, ex. 250 => 25.0C
| -30 to 75C, 10x C, ex. 250 => 25.0C
| -
|-
|-
| 10905
| 10905
Line 1,282: Line 1,454:
| Time, hhmm
| Time, hhmm
| Ex. 8:05 => 0x0805, 18:30 => 0x121E (18=0x12, 30=0x1E)
| Ex. 8:05 => 0x0805, 18:30 => 0x121E (18=0x12, 30=0x1E)
| -
|-
|-
| 10906
| 10906
Line 1,287: Line 1,460:
| Binary
| Binary
| 0x0..0xF [b3-b0, 0..1]<br>Ex. 0x01=>64=>00000001<br>b0=1, rotating heat exchanger
| 0x0..0xF [b3-b0, 0..1]<br>Ex. 0x01=>64=>00000001<br>b0=1, rotating heat exchanger
| DIP switch status
| System configuration/DIP switch status
| b0-Heat exchange type (0-RECU/1-REGO), <br>b1-Heater type (0-Electric/1-Water), <br>b2-Fan type (0-AC/1-EC), <br>b3-OVR-mode (0-All fans/1-Exhaust fan stop)<br>(1-On, 0-Off)
| b0-Heat exchange type (0-RECU/1-REGO), <br>b1-Heater type (0-Electric/1-Water), <br>b2-Fan type (0-AC/1-EC), <br>b3-OVR-mode (0-All fans/1-Exhaust fan stop)<br>(1-On, 0-Off)
| -
|-
|-
| 10907
| 10907
Line 1,296: Line 1,470:
| Alarm status (warnings)
| Alarm status (warnings)
| 14-Service, 13-Heater off, 11-Rotor stop
| 14-Service, 13-Heater off, 11-Rotor stop
| -
|-
|-
| 10908
| 10908
Line 1,303: Line 1,478:
| Alarm status (stop code)
| Alarm status (stop code)
| 3-Rotor stop, <br>4-Heater overheating, <br>9-Supply sensor B1, <br>19-Air temp. low, <br>20-Air temp. high, <br>27-Water temp. low, <br>28-Frost possibility
| 3-Rotor stop, <br>4-Heater overheating, <br>9-Supply sensor B1, <br>19-Air temp. low, <br>20-Air temp. high, <br>27-Water temp. low, <br>28-Frost possibility
| -
|-
|-
|}
|}

Latest revision as of 15:40, 18 April 2024

Komfovent 200ve wiring diagram.png
Komfovent c4 plus logic board front.jpg
Komfovent c4 plus logic board back.jpg
Komfovent 200 dissassembly diagram.png

Domekt Komfovent C4 control board is a AHU (Air Handling Unit) for use in a balanced HVAC system. The C4 is an older standard use from approx. 2010 to 2016.

If you have a unit without a control panel or want to interface the unit with an external automation. ex. Home Assistant, the following data will make that possible.

To make sure the unit works at all, jump the FC-wires together and the unit should start spinning at max. after three seconds. This confirms that the MCU works as expected.

Tools

To manually interface with the unit over Modbus, I would recommend trying the trail version of Modbus Poll. You will have a complete control interface and can easily send queries and receive responses from the unit.

Later you can use Home Assistant to build an entire control panel, better than what is provided by the OEM.

Connection

Connect the unit to a computer using the provided RS485/ModBus cable extruding from the top. There is no need to add 820 Ohm 5V pull-up/gnd pull-down or 120 Ohm termination. It works fine as is.

Komfovent c4 pinout.png

The pin-out is as the following:

RJ-45 flat cable Wire color Function
Pin 1 - Not used
Pin 2 - Not used
Pin 3 Red +24VDC
Pin 4 Yellow RS485 A+
Pin 5 Green RS485 B-
Pin 6 White Gnd
Pin 7 - Not used
Pin 8 - Not used

Modbus settings

Domekt c4 plus dip switches.png

To establish a working connection, it's important to match the following connection parameters. A single wrong setting will make the connection not work at all.

Bits per second/baudrate 19200
Data bits/word length 8
Parity Even
Stop bits 1

It is also important to use the correct Modbus ID. It's the identifier on the bus and has to be correct in order for communication to happen with the AHU.

The C4 unit has a different Modbus ID than later models, so make sure to double check. Either of the following will work with only one unit on the Modbus line.

Modbus ID 20 (specific C4 identification address)
254 (common identification address)

Register list

The C4 unit uses the following Modbus data register functions to read and write data.

A CR2032 battery keeps the registers concurrent when the unit is unplugged, ex. the time and date. Needs replacing after 8 years.

The unit will respond 01 Illegal register or 01 Illegal data register if you are trying to access something that does not exist. If you receive Timeout responses, make sure you use Modbus ID 20, cabling is correct, and the unit is plugged into the mains.

Description Modbus protocol Function description Unit properties
Read data Function code 03 Read Holding Registers / analog output holding registers Operation status, temperatures, fans speed, and etc.
Write data single register Function code 06 Preset Single Register / analog output holding register Turn on/off unit, set temperature, change auto/manual mode
Write multiple data registers Function code 16 Preset Multiple Registers / two analog output holding registers Set multiple individual registers at once, similar to 06

Controller registers available on the C4 unit. When manually inquiring the unit, use the actual register address. This is because Domekt offsets the register address by add 9000 and subtract -1, ex. register address 1000 => 99999.

  • EC = Stepper type fan motor, digitally controlled - DIP switch 3 set to ON
  • AC = Regular alternating current type motor, transformer controlled - DIP switch 3 set to OFF

General

13 registers

Modbus register actual Type Access Range Description Data values Default value
9999 Read/write Integer 0..1 AHU start/stop control 1-Start, 0-Stop -
10000 Read/write Integer 0..1 Season (heating permitted or prohibited) 1-Winter, 0-Summer (heater off) 1
10001 Read Integer 0..14 Alarm status (warnings) 14-Service, 13-Heater off, 11-Rotor stop -
10002 Read Binary 0x0..0xF [b3-b0, 0..1]
Ex. 0x01=>64=>00000001
b0=1, rotating heat exchanger
System configuration/DIP switch status b0-Heat exchange type (0-RECU/1-REGO),
b1-Heater type (0-Electric/1-Water),
b2-Fan type (0-AC/1-EC),
b3-OVR-mode (0-All fans/1-Exhaust fan stop)
(1-On, 0-Off)
-
10003 Read/write 2x Char/Int8 0x0000..0x183B Time, hhmm Ex. 8:05 => 0x0805, 18:30 => 0x121E (18=0x12, 30=0x1E) -
10004 Read/write Integer 1-7 Day of the week 1-Mon, 2-Tue, 3-Wed, 4-Thu, 5-Fri, 6-Sat, 7-Sun -
10005 Read/write 2x Char/Int8 0x0101..0x0C1F Month-day date, mmdd Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F) -
10006 Read/write Integer 2010-2200 Year date, yyyy Ex. 2023 -
10007 Read Binary 0x00..0x7F [b7-b0, 0..1]
Ex. 0x40=>64=>00000010
b1=1, supply sensor B1 fault
Alarm status (stop flags) b1-Supply sensor B1,
b2-Heater overheating,
b3-Water temp. low,
b4-Rotor stop,
b5-Frost possibility,
b6-Air temp. high,
b7-Air temp. low
(1-Fault, 0-None)
-
10008 Read Integer 0..28 Alarm status (stop code) 3-Rotor stop,
4-Heater overheating,
9-Supply sensor B1,
19-Air temp. low,
20-Air temp. high,
27-Water temp. low,
28-Frost possibility
-
10009 Read/write Integer 1..100 Modbus ID, default 20 Ex. 20 20
10010 Read/write Integer 0..1 External heater control signal type 0-0..12V analog voltage-type,
1-12V digital PWM-type
(always 0 if heater configured as water type)
-
10011 Read - - Unknown -

Ventilation

14 registers

Modbus register actual Type Access Range Description Data values Default value
10099 Read/write Integer 1..3 Ventilation intensity level (manual mode) 1-Low fan speed (60VAC),
2-Normal fan speed (recommended) (150VAC),
3-High fan speed (230VAC)
2
10100 Read Integer 0..4 Ventilation intensity level current 0-Standby,
1-Low fan speed,
2-Normal fan speed,
3-High fan speed,
4-Override mode (OVR-register enabled or FC-wiring closed)
-
10101 Read/write Integer 0..1 Control mode (Auto/Manual) (no Comfort or Economy mode available) 0-Manual (preset fan speed), 1-Auto (schedule) 0
10102 Read/write Integer 20..100 / 0 Supply ventilation intensity level 1 (EC-type fan) 20 to 100% (EC-fan only) -
10103 Read/write Integer 20..100 / 0..2 Supply ventilation intensity level 2 (EC-type fan / AC-type fan) 20 to 100% (EC-fan), 0 to 2 (AC-fan) 2
10104 Read/write Integer 20..100 / 0 Supply ventilation intensity level 3 (EC-type fan) 20 to 100% (EC-fan only) -
10105 Read/write Integer 20..100 / 0 Supply ventilation intensity level 4 (EC-type fan) 20 to 100% (EC-fan only) -
10106 Read/write Integer 20..100 / 0 Exhaust ventilation intensity level 1 (EC-type fan) 20 to 100% (EC-fan only) -
10107 Read/write Integer 20..100 / 0..2 Exhaust ventilation intensity level 2 (EC-type fan / AC-type fan) 20 to 100% (EC-fan), 0 to 2 (AC-fan) 2
10108 Read/write Integer 20..100 / 0 Exhaust ventilation intensity level 3 (EC-type fan) 20 to 100% (EC-fan only) -
10109 Read/write Integer 20..100 / 0 Exhaust ventilation intensity level 4 (EC-type fan) 20 to 100% (EC-fan only) -
10110 Read/write Integer 0..1 Override/OVR-mode, enables fan override intensity level for a set time period 0-Disable, 1-Enable - DIP switch 4 set to ON will disable the exhaust fan, or OFF to leave both fans running 0
10111 Read/write Integer 1..90 Override mode timer duration 1 to 90 minutes 30
10112 Read Integer 0..90 Override timer count down 0 to 90 minutes -

Scheduler

63 registers

Modbus register actual Type Access Range Description Data values Default value
10199 Read/write 2x Char/Int8 0x0000..0x183B Mon1 start time Ex. 08:05 => 0x0805 -
10200 Read/write 2x Char/Int8 0x0000..0x183B Mon1 stop time Ex. 15:05 => 0x0F05 -
10201 Read/write 2x Char/Int8 0x0000..0x183B Mon2 start time Ex. 08:05 => 0x0805 -
10202 Read/write 2x Char/Int8 0x0000..0x183B Mon2 stop time Ex. 15:05 => 0x0F05 -
10203 Read/write 2x Char/Int8 0x0000..0x183B Mon3 start time Ex. 08:05 => 0x0805 -
10204 Read/write 2x Char/Int8 0x0000..0x183B Mon3 stop time Ex. 15:05 => 0x0F05 -
10205 Read/write 2x Char/Int8 0x0000..0x183B Tue1 start time Ex. 08:05 => 0x0805 -
10206 Read/write 2x Char/Int8 0x0000..0x183B Tue1 stop time Ex. 15:05 => 0x0F05 -
10207 Read/write 2x Char/Int8 0x0000..0x183B Tue2 start time Ex. 08:05 => 0x0805 -
10208 Read/write 2x Char/Int8 0x0000..0x183B Tue2 stop time Ex. 15:05 => 0x0F05 -
10209 Read/write 2x Char/Int8 0x0000..0x183B Tue3 start time Ex. 08:05 => 0x0805 -
10210 Read/write 2x Char/Int8 0x0000..0x183B Tue3 stop time Ex. 15:05 => 0x0F05 -
10211 Read/write 2x Char/Int8 0x0000..0x183B Wed1 start time Ex. 08:05 => 0x0805 -
10212 Read/write 2x Char/Int8 0x0000..0x183B Wed1 stop time Ex. 15:05 => 0x0F05 -
10213 Read/write 2x Char/Int8 0x0000..0x183B Wed2 start time Ex. 08:05 => 0x0805 -
10214 Read/write 2x Char/Int8 0x0000..0x183B Wed2 stop time Ex. 15:05 => 0x0F05 -
10215 Read/write 2x Char/Int8 0x0000..0x183B Wed3 start time Ex. 08:05 => 0x0805 -
10216 Read/write 2x Char/Int8 0x0000..0x183B Wed3 stop time Ex. 15:05 => 0x0F05 -
10217 Read/write 2x Char/Int8 0x0000..0x183B Thu1 start time Ex. 08:05 => 0x0805 -
10218 Read/write 2x Char/Int8 0x0000..0x183B Thu1 stop time Ex. 15:05 => 0x0F05 -
10219 Read/write 2x Char/Int8 0x0000..0x183B Thu2 start time Ex. 08:05 => 0x0805 -
10220 Read/write 2x Char/Int8 0x0000..0x183B Thu2 stop time Ex. 15:05 => 0x0F05 -
10221 Read/write 2x Char/Int8 0x0000..0x183B Thu3 start time Ex. 08:05 => 0x0805 -
10222 Read/write 2x Char/Int8 0x0000..0x183B Thu3 stop time Ex. 15:05 => 0x0F05 -
10223 Read/write 2x Char/Int8 0x0000..0x183B Fri1 start time Ex. 08:05 => 0x0805 -
10224 Read/write 2x Char/Int8 0x0000..0x183B Fri1 stop time Ex. 15:05 => 0x0F05 -
10225 Read/write 2x Char/Int8 0x0000..0x183B Fri2 start time Ex. 08:05 => 0x0805 -
10226 Read/write 2x Char/Int8 0x0000..0x183B Fri2 stop time Ex. 15:05 => 0x0F05 -
10227 Read/write 2x Char/Int8 0x0000..0x183B Fri3 start time Ex. 08:05 => 0x0805 -
10228 Read/write 2x Char/Int8 0x0000..0x183B Fri3 stop time Ex. 15:05 => 0x0F05 -
10229 Read/write 2x Char/Int8 0x0000..0x183B Sat1 start time Ex. 08:05 => 0x0805 -
10230 Read/write 2x Char/Int8 0x0000..0x183B Sat1 stop time Ex. 15:05 => 0x0F05 -
10231 Read/write 2x Char/Int8 0x0000..0x183B Sat2 start time Ex. 08:05 => 0x0805 -
10232 Read/write 2x Char/Int8 0x0000..0x183B Sat2 stop time Ex. 15:05 => 0x0F05 -
10233 Read/write 2x Char/Int8 0x0000..0x183B Sat3 start time Ex. 08:05 => 0x0805 -
10234 Read/write 2x Char/Int8 0x0000..0x183B Sat3 stop time Ex. 15:05 => 0x0F05 -
10235 Read/write 2x Char/Int8 0x0000..0x183B Sun1 start time Ex. 08:05 => 0x0805 -
10236 Read/write 2x Char/Int8 0x0000..0x183B Sun1 stop time Ex. 15:05 => 0x0F05 -
10237 Read/write 2x Char/Int8 0x0000..0x183B Sun2 start time Ex. 08:05 => 0x0805 -
10238 Read/write 2x Char/Int8 0x0000..0x183B Sun2 stop time Ex. 15:05 => 0x0F05 -
10239 Read/write 2x Char/Int8 0x0000..0x183B Sun3 start time Ex. 08:05 => 0x0805 -
10240 Read/write 2x Char/Int8 0x0000..0x183B Sun3 stop time Ex. 15:05 => 0x0F05 -
10241 Read/write Integer 0..3 Mon1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10242 Read/write Integer 0..3 Mon2 ventilation level (fan speed) 0 to 3 -
10243 Read/write Integer 0..3 Mon3 ventilation level (fan speed) 0 to 3 -
10244 Read/write Integer 0..3 Tue1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10245 Read/write Integer 0..3 Tue2 ventilation level (fan speed) 0 to 3 -
10246 Read/write Integer 0..3 Tue3 ventilation level (fan speed) 0 to 3 -
10247 Read/write Integer 0..3 Wed1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10248 Read/write Integer 0..3 Wed2 ventilation level (fan speed) 0 to 3 -
10249 Read/write Integer 0..3 Wed3 ventilation level (fan speed) 0 to 3 -
10250 Read/write Integer 0..3 Thu1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10251 Read/write Integer 0..3 Thu2 ventilation level (fan speed) 0 to 3 -
10252 Read/write Integer 0..3 Thu3 ventilation level (fan speed) 0 to 3 -
10253 Read/write Integer 0..3 Fri1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10254 Read/write Integer 0..3 Fri2 ventilation level (fan speed) 0 to 3 -
10255 Read/write Integer 0..3 Fri3 ventilation level (fan speed) 0 to 3 -
10256 Read/write Integer 0..3 Sat1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10257 Read/write Integer 0..3 Sat2 ventilation level (fan speed) 0 to 3 -
10258 Read/write Integer 0..3 Sat3 ventilation level (fan speed) 0 to 3 -
10259 Read/write Integer 0..3 Sun1 ventilation level (fan speed) 0-Standby, 1-Low, 2-Normal, 3-High -
10260 Read/write Integer 0..3 Sun2 ventilation level (fan speed) 0 to 3 -
10261 Read/write Integer 0..3 Sun3 ventilation level (fan speed) 0 to 3 -


Temperature

6 registers

Modbus register actual Type Access Range Description Data values Default value
10299 Read Integer -300..750 Supply air temperature, C (sensor B1, after heat exchanger and heater element, to rooms) -30 to 75C, 10x C, ex. 250 => 25.0C -
10300 Read/write Integer 100..400 Supply set point temperature, C (for calculation of recuperation, heating levels) 10 to 40C, 10x C, ex. 25.0C => 250 23
10301 Read/write Integer -90..90 Temperature correction, C (time based, lower or raise temperature in a set period) -9 to +9C, 10x C, ex. +4.5C => 45 0
10302 Read/write 2x Char/Int8 0x0000..0x183B Temperature correction start time Ex. 08:05 => 0x0805 -
10303 Read/write 2x Char/Int8 0x0000..0x183B Temperature correction stop time Ex. 15:05 => 0x0F05 (15=0x0F, 05=0x05) -
10304 Read Integer -100..1100 Water temperature, C (external, sensor B5, if installed, DIP switch 2 set to ON) -10 to 110C, 10x C, ex. 320 => 32.0C -

Operation control panel (not in tech doc)

29 registers

Modbus register actual Type Access Range Description Data values Default value
10399 Read Binary 0x0..0xF [b3-b0, 0..1]
Ex. 0x01=>64=>00000001
b0=1, rotating heat exchanger
System configuration/DIP switch status b0-Heat exchange type (0-RECU/1-REGO),
b1-Heater type (0-Electric/1-Water),
b2-Fan type (0-AC/1-EC),
b3-OVR-mode (0-All fans/1-Exhaust fan stop)
(1-On, 0-Off)
-
10400 Read/write Integer 0..1 AHU start/stop control 1-Start, 0-Stop -
10401 Read/write Integer 0..1 Control mode (Auto/Manual) (no Comfort or Economy mode available) 0-Manual (preset fan speed), 1-Auto (schedule) 0
10402 Read/write Integer 1..3 Ventilation intensity level (in manual mode) 1-Low fan speed (60VAC),
2-Normal fan speed (recommended) (150VAC),
3-High fan speed (230VAC)
2
10403 Read Integer 0..4 Ventilation intensity level current 0-Standby,
1-Low fan speed,
2-Normal fan speed,
3-High fan speed,
4-Override mode (OVR-register enabled or FC-wiring closed)
-
10404 Read Integer 0..100 Supply fan level 0 set point 0 to 100% 0
10405 Read Integer 0..100 Supply fan level 1 set point 0 to 100% 20
10406 Read Integer 0..100 Supply fan level 2 set point 0 to 100% 60
10407 Read Integer 0..100 Exhaust fan level 0 set point 0 to 100% 0
10408 Read Integer 0..100 Exhaust fan level 1 set point 0 to 100% 20
10409 Read Integer 0..100 Exhaust fan level 2 set point 0 to 100% 60
10410 Read Integer 0..100 Override supply fan level set point 0 to 100% 100
10411 Read Integer 0..100 Override exhaust fan level set point (for standby/0%, set DIP switch 4 to ON) 0 to 100% 100
10412 Read/write Integer 0..300 Supply set point temperature, C (for calculation of recuperation, heating levels) 0 to 30C, 10x C, ex. 25.0C => 250 23
10413 Read/write Integer 0..1 Season (heating permitted or prohibited) 1-Winter, 0-Summer (air heating off) 1
10414 Read/write Integer -90..90 Temperature correction, C (time based, lower or raise temperature in a set period) -9 to +9C, 10x C, ex. +4.5C => 45 0
10415 Read/write 2x Char/Int8 0x0000..0x183B Temperature correction start time Ex. 08:05 => 0x0805 -
10416 Read/write 2x Char/Int8 0x0000..0x183B Temperature correction stop time Ex. 15:05 => 0x0F05 (15=0x0F, 05=0x05) -
10417 Read Integer -300..750 Supply air temperature, C (after heat exchanger and heater element, to rooms) -30 to 75C, 10x C, ex. 250 => 25.0C -
10418 Read Integer -100..1100 Water temperature, C (external, if installed, DIP switch 2 set to ON) -10 to 110C, 10x C, ex. 320 => 32.0C -
10419 Read Integer 0..100 Recuperation level (rotating heat exchanger, DIP switch 1 set to ON - not adjustable directly only through supply set point temperature) 0 to 100% -
10420 Read Integer 0..100 Supply fan level current 0 to 100% -
10421 Read Integer 0..100 Exhaust fan level current 0 to 100% -
10422 Read Integer 0..100 Electric heater level current (heating element, DIP switch 2 set to OFF) 0 to 100% -
10423 Read Integer 0..100 Water heating level current (external, if installed, DIP switch 2 set to ON) 0 to 100% -
10424 Read Integer 0..100 Water cooling level current (external, if installed, DIP switch 2 set to ON) 0 to 100% -
10425 Read - - Unknown -
10426 Read Integer 0..14 Alarm status (warnings) 14-Service, 13-Heater off, 11-Rotor stop -
10427 Read Integer 0..28 Alarm status (stop code) 3-Rotor stop,
4-Heater overheating,
9-Supply sensor B1,
19-Air temp. low,
20-Air temp. high,
27-Water temp. low,
28-Frost possibility
-

Alarm history

701 registers

Modbus register actual Type Access Range Description Data values Default value
10499 Read/write Integer 0..50 Alarm history count Length of log to keep -
10500 Read Integer 2010..2200 Alarm1 (newest) year Ex. 2023 -
10501 Read 2x Char/Int8 0x0101..0x0C1F Alarm1 (newest) month-day Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F) -
10502 Read 2x Char/Int8 0x0000..0x183B Alarm1 (newest) hour-minute Ex. 08:05 => 0x0805 -
10503 Read Integer 0..28 Alarm1 (newest) alarm stop and warning code Ex. 14-Service -
.. Alarm2..Alarm49
10696 Read Integer 2010..2200 Alarm50 (oldest) year Ex. 2023 -
10697 Read 2x Char/Int8 0x0101..0x0C1F Alarm50 (oldest) month-day Ex. 9th May => 0x0509, 31th Sept => 0x091F (Sept=0x09, 31=0x1F) -
10698 Read 2x Char/Int8 0x0000..0x183B Alarm50 (oldest) hour-minute Ex. 08:05 => 0x0805 -
10699 Read Integer 0..28 Alarm50 (oldest) alarm stop and warning code Ex. 14-Service -

Misc

4 registers, 4 registers

Modbus register actual Type Access Range Description Data values Default value
10799 Read Integer 0..100 Internal heater level current (heating element, DIP switch 2 set to OFF) 0 to 100% -
10800 Read Integer 0..100 External/water heating level current (external, if installed, DIP switch 2 set to ON) 0 to 100% -
10801 Read Integer 0..100 Service time counter 0 to 100, when reached 100, it is service time (alarm warning 14) -
10802 Read Integer 0..200 AHU software program version 100-V1.00, 103-V1.03 -
10889 Read/write Integer -100..100 V1 0.10V calibration value -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory) 0
10890 Read/write Integer -100..100 V2 0.10V calibration value -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory) 0
10891 Read/write Integer -100..100 External heater level calibration value -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory) 0
10892 Read/write Integer -100..100 Return water temperature calibration value -10..+10%, 10x, 1% => 10 (Write 0x99C4 to store to memory) 0

Control panel (read-only)

10 registers

Modbus register actual Type Access Range Description Data values Default value
10899 Read Integer 0..1 AHU start/stop control 1-Start, 0-Stop -
10900 Read Integer 0..1 Season (heating permitted or prohibited) 1-Winter, 0-Summer (heater off) -
10901 Read Integer 0..1 Control mode (Auto/Manual) 0-Manual (preset fan speed), 1-Auto (schedule) -
10902 Read Integer 0..4 Ventilation intensity level current 0-Standby,
1-Low fan speed,
2-Normal fan speed,
3-High fan speed,
4-Override mode (OVR-register enabled or FC-wiring closed)
-
10903 Read Integer 100..400 Supply set point temperature, C 10 to 40C, 10x C, ex. 25.0C => 250 -
10904 Read Integer -300..750 Supply air temperature, C -30 to 75C, 10x C, ex. 250 => 25.0C -
10905 Read/write 2x Char/Int8 0x0000..0x183B Time, hhmm Ex. 8:05 => 0x0805, 18:30 => 0x121E (18=0x12, 30=0x1E) -
10906 Read Binary 0x0..0xF [b3-b0, 0..1]
Ex. 0x01=>64=>00000001
b0=1, rotating heat exchanger
System configuration/DIP switch status b0-Heat exchange type (0-RECU/1-REGO),
b1-Heater type (0-Electric/1-Water),
b2-Fan type (0-AC/1-EC),
b3-OVR-mode (0-All fans/1-Exhaust fan stop)
(1-On, 0-Off)
-
10907 Read Integer 0..14 Alarm status (warnings) 14-Service, 13-Heater off, 11-Rotor stop -
10908 Read Integer 0..28 Alarm status (stop code) 3-Rotor stop,
4-Heater overheating,
9-Supply sensor B1,
19-Air temp. low,
20-Air temp. high,
27-Water temp. low,
28-Frost possibility
-